My six US2000B Plus never charge beyond 80 % — is it the Growatt inverter?

Mes six US2000B Plus ne chargent jamais au-delà de 80 % : est-ce l'onduleur Growatt ?

Preguntada el · Actualizada · 1 respuesta

Respuesta corta

Not the inverter. In three of the six batteries a few cells reach 3.55–3.65 V while the others stay near 3.35 V, so their BMS stops the charge; the stack average stays near 80 %. Slower charging does not help: the cells must be rebalanced by those batteries' BMS, a warranty matter for the installer (BatteryView).

Cliente J. 🇫🇷 Francia Pregunta
🇬🇧 Inglés · Traducción al inglés por nuestro equipo

Over the last 90 days I can no longer count the times the batteries should have charged to 100 % but stopped at 80 %, sending the solar surplus to the grid.

Last night I tried a slow charge at 10 % power (337 W for 6 batteries) from 58 %. It stopped at 80 % again — impossible to charge to 100 %, whatever the method (solar, grid, full power or slow charge).

My reseller says the problem comes from the Growatt inverter and sends me to their support. I don't believe it. Do you have a solution?

Original · Français

Au cours des 90 derniers jours, je ne compte plus le nombre de fois où les batteries auraient dû charger à 100 % mais se sont stoppées à 80 %, générant du surplus solaire injecté au réseau.

J'ai tenté cette nuit une charge lente à 10 % de puissance (337 W pour 6 batteries) à partir de 58 %. La charge s'est encore stoppée à 80 %… impossible de charger à 100 %, peu importe la manière (solaire, réseau, pleine puissance ou charge lente).

Le revendeur me dit que le problème provient de l'onduleur Growatt et m'envoie vers leur SAV. Je n'y crois pas. Avez-vous une solution ?

Equipo Pylon-MonitorRespuesta oficial
🇬🇧 Inglés

We looked at your night and morning readings, battery by battery and cell by cell: it would not be the Growatt.

Batteries 2, 5 and 6 are fine: they reach 100 % and their 15 cells stay within 11–15 mV of each other.

Batteries 1, 3 and 4 each have a few cells that fill up before the others. Your slow charge went well until 5 a.m.; then those cells rose to 3.55–3.58 V while the others stayed near 3.35 V, and the battery's BMS stopped the charge to protect them. Charging slower or longer changes nothing.

These three batteries also show a wrong state of charge (57 to 70 %) and a voltage alarm, which keeps the stack average near 80 %. Their BMS should rebalance the cells in exactly this situation, yet none of them reported any balancing, although the same BMS version does on other installations.

Our advice: present this to your installer as a Pylontech warranty request for batteries 1, 3 and 4 — a check and rebalancing with BatteryView, a BMS update, or a replacement if balancing does not come back.

Original · Français

Nous avons examiné vos relevés de la nuit et du matin, batterie par batterie et cellule par cellule : ce ne serait pas le Growatt.

Vos batteries 2, 5 et 6 vont bien : elles atteignent 100 % et leurs 15 cellules restent à 11-15 mV les unes des autres.

Les batteries 1, 3 et 4 ont chacune quelques cellules qui se remplissent avant les autres. Votre charge lente s'est bien passée jusqu'à 5 h ; ensuite ces cellules sont montées à 3,55-3,58 V pendant que les autres restaient vers 3,35 V, et le BMS de la batterie a coupé la charge pour les protéger. Charger plus lentement ou plus longtemps n'y change rien.

Ces trois batteries affichent aussi un niveau de charge erroné (57 à 70 %) et une alarme de tension, ce qui fait plafonner la moyenne du parc vers 80 %. Leur BMS devrait rééquilibrer les cellules justement dans cette situation, or aucun n'a signalé d'équilibrage, alors que la même version de BMS le fait sur d'autres installations.

Notre conseil : présenter ces éléments à votre installateur comme une demande de garantie Pylontech pour les batteries 1, 3 et 4 — contrôle et rééquilibrage avec BatteryView, mise à jour du BMS, ou remplacement si l'équilibrage ne revient pas.

¿Le ha sido útil esta respuesta?
#US2000B Plus#cell imbalance#BMS#charge stops at 80 %#Growatt